GUIDELINE FOR SETTING A1000 / V1000 INVERTER PARAMETERS FOR COMPRESSOR APPLICATION


TYPICAL CASE STUDY
Compressor type : Reciprocating
Motor 55kW, 98 Amp, 4 Pole , 1470 RPM, 50Hz, Motor no load current : 30 Amp
Load pressure : 6 kg / sq. cm
Unload pressure : 7 kg / sq. cm
Pressure transmitter to be used : approximately 1.2 times unload pressure
Pressure transmitter selected : 10 kg / sq. cm
Pressure transmitter output signal preferably : 4-20 mA proportional to 0-10 kg / sq. cm